Close Menu
    Facebook X (Twitter) Instagram
    Trending
    • ⚡ Cable Types in Distribution: XLPE vs PILC vs Aerial Bundled Cables
    • ⚡ Smart Grid in Distribution: Role, Challenges & Indian Scenario
    • ⚡ Power Factor Correction in Distribution Systems
    • ⚡ Understanding Distribution Protection: Fuses, Relays & Reclosers
    • ⚡ Voltage Drop in Distribution Lines: Causes, Calculation & Correction
    • 🛠️ Distribution Transformer Maintenance: Checklist and Tips
    • INTRODUCTION TO SUBSTATION EARTHING
    • Maintenance of GIS (Gas-Insulated Switchgear)
    Electric Know How
    • Home
    • Generation
      • Hydropower Station
      • Thermal Power Station
      • DISTRIBUTED ENERGY SOURCES
      • Diesel Generator
      • Industrial Tools
      • DC System-Generating Stations
    • Transmission
      • High Voltage DC Transmission
      • High Voltage AC Transmission
        • Transmission line – An Overview
        • TRANSMISSION TOWER CONFIGURATION
        • Transmission Towers-Key Features
    • Distribution
      • ⚡ Understanding Electrical Distribution Systems: Basics to Architecture
      • ⚡ Top 5 Faults in Distribution Lines and How to Fix Them
      • 🛠️ Distribution Transformer Maintenance: Checklist and Tips
    • Protection
      • Power System Protection
        • Types of Fault in Power System
        • Relay Setting Calculation for Substation
        • Circuit Breaker
          • Nameplate details of SF6 Circuit Breaker
          • Major parameters of a circuit breaker
          • What is the use of an anti-pumping relay?
          • What is an IR Value Test in a Circuit Breaker? An overview
          • Testing of Circuit Breaker
        • Key Components of Control & Relay Panel
          • Relay Setting Calculation for Substation
          • Trip Circuit Supervision Relay
          • Three Phase Control Wiring
        • Switching Surges and Its Remedies
      • OVERVIEW OF TRANSFORMER PROTECTION
        • Differential Protection of Transformer
      • OVERVIEW OF GENERATOR PROTECTION
      • Distance Protection
      • Electrical Safety
    • Switchgear
      • Electrical Sub-Station
        • BATTERY SYSTEM IN GRID SUBSTATION
        • Operation of Float Cum Boost Charger
        • Protection Circuitry of Battery Charger
        • Power Transformer
          • INSULATION RESISTANCE OF TRANSFORMER
          • WTI AND OTI in Power Transformer
          • Transformer Oil Dielectric strength
          • On Load Tap Changing of Transformer
          • TRANSFORMER MAINTENANCE
        • Sub-Station Operation
        • Multiplying Factor for Energy Meter
      • Current Transformer
        • Nameplate Detail of Current Transformer – A Detail Guide
        • Current Transformer Knee Point Test – A Detailed Overview
        • What is a Current Transformer Polarity Test- Detailed Guide
        • Ratio test of Current Transformer
      • Potential Transformer
      • Isolator in Substation
        • Nameplate Detail of Isolators/Dis-connectors- A Detail Guide
      • Electrical Busbar
      • Insulators
      • Clamps and Connectors
      • Fire Fighting System
      • Lightening Arrester
        • LCM Test of a Lightning Arrestor – An Overview
      • Gas Insulated Substation
        • Local Control Cubicle
        • SF6 circuit breaker gas compartment
        • Maintenance of GIS (Gas-Insulated Switchgear)
    • Q&A
      • FAQS ON Current Transformer
      • POWER SYSTEM
      • FAQ ON BUSBAR
    Electric Know How
    Home»Switchgear»INSULATION RESISTANCE OF TRANSFORMER
    Switchgear

    INSULATION RESISTANCE OF TRANSFORMER

    madhusmitaBy madhusmita25 November 2022Updated:26 May 2024No Comments3 Mins Read
    Facebook Twitter Pinterest LinkedIn Tumblr Email
    Share
    Facebook Twitter LinkedIn Pinterest Email

    Table of Contents

    Toggle
    • INTRODUCTION
      • Why Insulation Resistance test is performed?
      • How Insulation Resistance Test is performed for the transformer?
      • TEST PROCEDURE
      •  Safety precautions during Test
      • IR Values for Transformer winding
      • SUMMARY

    INTRODUCTION

    Insulation Resistance is the resistance between two electrical conductors or two systems of conductors separated by an insulating material.

    A high value of resistance means that very little current is escaping through the insulation. Conversely, a low value of resistance indicates a significant amount of current may be leaking through and along the insulation

    Insulation resistance needs to be maintained at a safe value to prevent production loss and to protect against electric shocks to humans.

    Why Insulation Resistance test is performed?

    In order to check the quality of insulation when a product is first manufactured and after the prolonged use of the product. Performing such tests at regular time intervals can detect impending insulation failures before they occur and prevent user accidents or costly product repairs.

    How Insulation Resistance Test is performed for the transformer?

    The Megger insulation tester is essentially a high-range resistance meter (ohmmeter) with a built-in direct-current generator. This meter is of special construction with current and voltage coils, enabling true ohms to be read directly, independent of the actual voltage applied. This method is non-destructive; that is, it does not cause deterioration of the insulation

    .

    Digital Insulation Resistance Testers.

    Apparatus Available

    • Hand-Driven Insulation Testers.
    • Digital Insulation Resistance Testers.
    • Multimeter Insulation Testers.
    • Digital Earth Insulation Testers.
    • Hand Cum Motorized Insulation Testers

    TEST PROCEDURE

    1. Isolate the transformer from the main supply and discharge after disconnecting all the phases.
    2. Short the tester leads. Set the voltage range as per the data given in the table.
    3. Identify the test points. Test between windings. Two winding transformers:(HV + LV) – GND,HV – (LV + GND),LV – (HV + GND)
    4. Test between windings and earth as per the connection diagram mentioned in the figure.
    5. Perform the test and record the result along with the measurement of temperature.
    WINDING RATED VOLTAGEIR TEST VOLTAGE
    <1000500
    1000-2500500-1000
    2501-50001000-2500
    5000-120002500-5000
    >120005000-10000

    IR TEST VOLTAGE

     Safety precautions during Test

    • Work on de-energized circuits whenever possible. Use proper lock-out/tag-out procedures.
    • Don’t touch any of the terminals during the test process.

    IR Values for Transformer winding

    IR Value (MΩ) = C X E (P-n) / (√KVA) Where C= 1.5 for Oil filled T/C with Oil Tank, 30 for Oil filled T/C without Oil Tank or Dry Type T/C.As per standard Insulation resistance should be approximately one megohm for each 1,000 volts of operating voltage.

    TRANSFORMER WINDING VALUES IN MOHMS

    SUMMARY

    Insulation resistance testing is an essential tool for assessing the health of power transformers and ensuring reliable operation in electrical power systems.

    Share. Facebook Twitter Pinterest LinkedIn Tumblr Email
    Previous ArticleOn Load Tap Changing of Transformer
    Next Article Electrical Safety
    madhusmita
    • Website
    • Facebook
    • Instagram
    • LinkedIn

    Related Posts

    ⚡ Smart Grid in Distribution: Role, Challenges & Indian Scenario

    16 May 2025

    ⚡ Power Factor Correction in Distribution Systems

    16 May 2025

    ⚡ Voltage Drop in Distribution Lines: Causes, Calculation & Correction

    16 May 2025

    Comments are closed.

    Archives
    Categories
    • Distribution (15)
    • Generation (10)
    • Protection (24)
    • Q&A (7)
    • Switchgear (48)
      • Nameplate Details (2)
    • testing (11)
    • Transmission (20)
    Recent Posts
    • ⚡ Cable Types in Distribution: XLPE vs PILC vs Aerial Bundled Cables
    • ⚡ Smart Grid in Distribution: Role, Challenges & Indian Scenario
    • ⚡ Power Factor Correction in Distribution Systems
    • ⚡ Understanding Distribution Protection: Fuses, Relays & Reclosers
    • ⚡ Voltage Drop in Distribution Lines: Causes, Calculation & Correction
    Certification Course
    Electric Volt

    Quick Links

    • Home
    • About Us
    • Contact Us

    Post Categories

    • Generation
    • Transmission
    • Distribution
    • Protection
    • Switchgear
    • Q&A

    Vip Link

    • Privacy Policy
    • Disclaimer
    • Terms and Conditions

    Contact Us

    • ele.mamohanty@optcl.co.in
    Linkedin