Close Menu
    Facebook X (Twitter) Instagram
    Trending
    • ⚡ Understanding Distribution Protection: Fuses, Relays & Reclosers
    • ⚡ Voltage Drop in Distribution Lines: Causes, Calculation & Correction
    • 🛠️ Distribution Transformer Maintenance: Checklist and Tips
    • INTRODUCTION TO SUBSTATION EARTHING
    • Maintenance of GIS (Gas-Insulated Switchgear)
    • Nameplate Detail of Isolators/Dis-connectors- A Detail Guide
    • What is the use of an anti-pumping relay?
    • Key Components of Control & Relay Panel
    Electric Know How
    • Home
    • Generation
      • Hydropower Station
      • Thermal Power Station
      • DISTRIBUTED ENERGY SOURCES
      • Diesel Generator
      • Industrial Tools
      • DC System-Generating Stations
    • Transmission
      • High Voltage DC Transmission
      • High Voltage AC Transmission
        • Transmission line – An Overview
        • TRANSMISSION TOWER CONFIGURATION
        • Transmission Towers-Key Features
    • Distribution
      • ⚡ Understanding Electrical Distribution Systems: Basics to Architecture
      • ⚡ Top 5 Faults in Distribution Lines and How to Fix Them
      • 🛠️ Distribution Transformer Maintenance: Checklist and Tips
    • Protection
      • Power System Protection
        • Types of Fault in Power System
        • Relay Setting Calculation for Substation
        • Circuit Breaker
          • Nameplate details of SF6 Circuit Breaker
          • Major parameters of a circuit breaker
          • What is the use of an anti-pumping relay?
          • What is an IR Value Test in a Circuit Breaker? An overview
          • Testing of Circuit Breaker
        • Key Components of Control & Relay Panel
          • Relay Setting Calculation for Substation
          • Trip Circuit Supervision Relay
          • Three Phase Control Wiring
        • Switching Surges and Its Remedies
      • OVERVIEW OF TRANSFORMER PROTECTION
        • Differential Protection of Transformer
      • OVERVIEW OF GENERATOR PROTECTION
      • Distance Protection
      • Electrical Safety
    • Switchgear
      • Electrical Sub-Station
        • BATTERY SYSTEM IN GRID SUBSTATION
        • Operation of Float Cum Boost Charger
        • Protection Circuitry of Battery Charger
        • Power Transformer
          • INSULATION RESISTANCE OF TRANSFORMER
          • WTI AND OTI in Power Transformer
          • Transformer Oil Dielectric strength
          • On Load Tap Changing of Transformer
          • TRANSFORMER MAINTENANCE
        • Sub-Station Operation
        • Multiplying Factor for Energy Meter
      • Current Transformer
        • Nameplate Detail of Current Transformer – A Detail Guide
        • Current Transformer Knee Point Test – A Detailed Overview
        • What is a Current Transformer Polarity Test- Detailed Guide
        • Ratio test of Current Transformer
      • Potential Transformer
      • Isolator in Substation
        • Nameplate Detail of Isolators/Dis-connectors- A Detail Guide
      • Electrical Busbar
      • Insulators
      • Clamps and Connectors
      • Fire Fighting System
      • Lightening Arrester
        • LCM Test of a Lightning Arrestor – An Overview
      • Gas Insulated Substation
        • Local Control Cubicle
        • SF6 circuit breaker gas compartment
        • Maintenance of GIS (Gas-Insulated Switchgear)
    • Q&A
      • FAQS ON Current Transformer
      • POWER SYSTEM
      • FAQ ON BUSBAR
    Electric Know How
    Home»Switchgear»What is an IR Value Test in a Circuit Breaker? An overview
    Switchgear

    What is an IR Value Test in a Circuit Breaker? An overview

    madhusmitaBy madhusmita13 November 2023Updated:16 May 2025No Comments4 Mins Read
    Facebook Twitter Pinterest LinkedIn Tumblr Email
    ??????
    Share
    Facebook Twitter LinkedIn Pinterest Email

    Circuit breakers are safety devices in our power system. They perform key functions of tripping during any fault. So keeping in view their functions, we must observe and test in regular intervals for their long-term operation in the power system to keep them working in safer mode. In this article, we are going to discuss an insulation resistance value test and how we can perform it.

    Table of Contents

    Toggle
    • IR Value Test in a Circuit Breaker:
      • ⚙️ Purpose of IR Test
    • Voltage Level for Different Circuit Breakers
    • Open Condition in Circuit Breaker
    • Key Tips While Performing IR Test:
      • ⚠️ Important Considerations
      • 📘 Standards and References
    • Conclusion:

    IR Value Test in a Circuit Breaker:

    ⚙️ Purpose of IR Test

    • To check the health of insulation in a circuit breaker.
    • To detect insulation degradation due to moisture, contamination, age, or thermal stress.
    • To prevent flashovers, equipment failure, or electrical hazards.

    There are different types of circuit breakers used in our power distribution grids for protection purposes:

    • SF6
    • Vacuum Circuit Breaker
    • Air Circuit Breaker

    We apply insulation resistance test on all types of circuit breakers in two conditions:

    • Open Condition
    • Closed Condition

    In the circuit breaker, one side (Red, Yellow, blue phase) of the circuit breaker is connected to the incoming from the bus bar, and a second side ((Red, Yellow, blue phase) is connected to the motor or feeder directly.

    So in case of open condition, the circuit bear is in the off state. In this condition, contactors in the circuit breaker will remain in the open state.

    On the other hand, in the closed condition, the contactors in the circuit breaker will remain closed and we can say the circuit breaker is in an ON state.  

    Voltage Level for Different Circuit Breakers

    According to the standard value, we need the value of DC voltage from the IR Testing Kit to apply to different capacities of circuit breakers. Here is a list of different circuit breakers’ capacity voltages and Megger Set voltages. 

    Serial No.Circuit Breaker Voltage Level Set Voltage
    1650500V DC
    21.1kV1kV DC
    33.3kV2.5kV DC
    46.6Kv and above5kV DC

    It means that if we have a 6.6kV circuit breaker, we can apply 5kV DC from the Megger Set to test the insulation resistance. These are standard values and similarly, the concept goes for other voltage cases.

    Open Condition in Circuit Breaker

    In case of the open condition, we will connect the positive probe of the Megger Set to any one of the incoming phases. Similarly, we will connect the negative probe of the Meggar set to the outgaining phase (the same outgoing phase as the incoming phase).

    You can understand the above concept by following the table indication:

    Sr. No.Incoming Pole-Outgoing PoleMegger Set IR Value (MΩ)
    1R-R­­­­­­­­­­­­­­­­­­­­From the Megger Output result
    2Y-YFrom the Megger Output result
    3B-BFrom the Megger Output result

    Here:

    R = Red Phase (incoming pole and outgoing pole)

    Y = Yellow Phase (incoming pole and outgoing pole)

    B = Blue Phase (incoming pole and outgoing pole)

    Following is the picture describing the same concept using incoming and outgoing poles in our circuit breaker in case of open condition:

    Circuit Breaker IR Test

    We will assess whether particular pole contacts are in an apart condition.

    Equipment Voltage LevelAcceptable IR Value (General Guideline)
    LV (<1kV)> 1 MΩ
    MV (1kV–33kV)> 100 MΩ
    HV (>33kV)> 200 MΩ – 1000 MΩ (or as per standard)

    Key Tips While Performing IR Test:

    Here are the following key points that one must consider while performing the IR Test:

    • You must apply appropriate voltage according to the industry standard.
    • Compare measure value with standard value to check the required results.
    • You can measure the IR value after making the circuit off and getting proper Line Clear from the appropriate authority.

    ⚠️ Important Considerations

    • Temperature and humidity affect IR readings (higher temperature or humidity = lower resistance).
    • Allow charging time when testing high-capacitance equipment.
    • Perform the test periodically for preventive maintenance.
    • After testing, discharge the breaker insulation before reconnecting.

    📘 Standards and References

    • IEEE Std 43: Guide for Testing Insulation Resistance
    • IEC 60060: High-voltage Test Techniques
    • NETA MTS: Maintenance Testing Specifications

    Conclusion:

    The insulation resistance test is important in a circuit breaker to detect the flow of electric current in conductive parts of a circuit breaker. It helps us to measure the leakage current possibilities. In the article, we have studied to procedure of the IR value test using the Megger Set.   

    electrical circuit breaker insulation resistance
    Share. Facebook Twitter Pinterest LinkedIn Tumblr Email
    Previous ArticleTesting of EHT Equipments: An Overview
    Next Article Current Transformer IR Test – A Detailed Guide
    madhusmita
    • Website
    • Facebook
    • Instagram
    • LinkedIn

    Related Posts

    ⚡ Voltage Drop in Distribution Lines: Causes, Calculation & Correction

    16 May 2025

    INTRODUCTION TO SUBSTATION EARTHING

    12 January 2025

    Maintenance of GIS (Gas-Insulated Switchgear)

    1 December 2024

    Comments are closed.

    Recent Posts
    • ⚡ Understanding Distribution Protection: Fuses, Relays & Reclosers
    • ⚡ Voltage Drop in Distribution Lines: Causes, Calculation & Correction
    • 🛠️ Distribution Transformer Maintenance: Checklist and Tips
    • INTRODUCTION TO SUBSTATION EARTHING
    • Maintenance of GIS (Gas-Insulated Switchgear)
    Certification Course
    Archives
    • May 2025
    • January 2025
    • December 2024
    • August 2024
    • July 2024
    • May 2024
    • March 2024
    • February 2024
    • January 2024
    • November 2023
    • October 2023
    • September 2023
    • August 2023
    • July 2023
    • June 2023
    • May 2023
    • April 2023
    • March 2023
    • December 2022
    • November 2022
    Categories
    • Distribution
    • Generation
    • Nameplate Details
    • Protection
    • Q&A
    • Switchgear
    • testing
    • Transmission
    Electric Volt

    Quick Links

    • Home
    • About Us
    • Contact Us

    Post Categories

    • Generation
    • Transmission
    • Distribution
    • Protection
    • Switchgear
    • Q&A

    Vip Link

    • Privacy Policy
    • Disclaimer
    • Terms and Conditions

    Contact Us

    • [email protected]
    Linkedin