Facebook Twitter Instagram
    Trending
    • LIST OF B.TECH/M.TECH PROJECT IDEAS (MATLAB SIMULATION)
    • Job Opportunities for Electrical Engineers 
    • Energy Meter Apex 100
    • Testing of Circuit Breaker
    • Faults in Distribution Lines
    • Distribution System Overview
    • Transmission Towers
    • TRANSFORMER MAINTENANCE
    Learn With Electric Know How
    • Home
    • Generation
      • Hydropower Station
      • Thermal Power Station
      • DISTRIBUTED ENERGY SOURCES
      • Diesel Generator
      • Industrial Tools
      • DC System-Generating Stations
    • Transmission
      • High Voltage DC Transmission
      • High Voltage AC Transmission
      • Three Phase Control Wiring
    • Distribution
      • Distribution System Overview
      • Faults in Distribution Lines
    • Protection
      • Power System Protection
        • Types of Fault in Power System
        • Circuit Breaker
      • OVERVIEW OF TRANSFORMER PROTECTION
        • Differential Protection of Transformer
      • OVERVIEW OF GENERATOR PROTECTION
      • Distance Protection
      • Electrical Safety
    • Switchgear
      • Electrical Sub-Station
        • BATTERY SYSTEM IN GRID SUBSTATION
        • Operation of Float Cum Boost Charger
        • Protection Circuitry of Battery Charger
        • Transformer
          • INSULATION RESISTANCE OF TRANSFORMER
          • WTI AND OTI in Power Transformer
          • Transformer Oil Dielectric strength
        • Sub-Station Operation
        • Multiplying Factor for Energy Meter
      • Current Transformer
      • Potential Transformer
      • Isolator in Substation
      • Electrical Busbar
      • Insulators
      • Clamps and Connectors
      • Fire Fighting System
      • Lightening Arrester
      • Gas Insulated Substation
        • Local Control Cubicle
        • SF6 circuit breaker gas compartment
    • Q&A
      • FAQS ON CT
      • POWER SYSTEM
      • FAQ ON BUSBAR
    Learn With Electric Know How
    Home»Switchgear»Testing of Circuit Breaker
    Switchgear

    Testing of Circuit Breaker

    madhusmitaBy madhusmitaMarch 18, 2023Updated:April 8, 2023No Comments5 Mins Read
    Facebook Twitter Pinterest LinkedIn Tumblr Email
    Share
    Facebook Twitter LinkedIn Pinterest Email

    Circuit Breaker is a critical component in the electric power system. Incorrect operation of circuit breakers can have disastrous consequences on the equipment connected downstream and the safety of substation personnel.  Because of their key role, circuit breakers are to be periodically tested and diagnosed. Timely intervention can not only extend the life of the contact but also avoid unscheduled breakdown of the circuit breaker.  

    Tests to be performed

    • Test for Timing of circuit breakers
      • Static & Dynamic contract resistance measurements are carried out. 
    • Test on auxiliaries equipment 
    • Operating coils and recharging mechanisms.   
    Testing Kit

    Visual Observation

    Visual observation shall include the following:

    • Air Pressure in case of ABCB / Gas pressure in case of SF6 breakers
      • Check for contamination  near operating releases
      • Check for abnormal sound/vibration during operation,
      • Corrosion  on parts of operating mechanisms, structures & supports

    Timing Test of CB

    • Closing Time
      • Opening Time
      • Close Open Time ( O-0.3sec-CO if applicable)
      • Time spread between poles
      • Recharging time of the operating device like
      •  motor charging, air releases, etc
      • Consumption & recording of currents of the shunt closing releases and shunt opening releases.
    • Mechanical travel characteristics  (if  feasible)

    Opening Time

    • The time between the instant of energizing the opening release of a circuit breaker which is in the closed position to the instant when arcing contact of all the poles has separated.
    • The opening time shall include all such auxiliary equipment necessary to open the circuit breaker and form an integral part of the circuit breaker.
    • Applicable to all CB which are tripped & operated by any form of auxiliary power. 

    Breaking Time

    • The interval of time between the beginning of the opening time of the mechanical switching device and the end of the arcing time.

    Closing Time -C

    • The interval of time between energizing the closing circuit of the circuit breaker which is in open position to the instant when the contacts touch in all poles. 
    • The closing time shall include all such auxiliary equipment necessary to close the circuit breaker and form an integral part of the circuit breaker.

    Close- Open Time- CO

    • The interval of time between the instant when the contacts touch in the first pole during a closing operation and the instant when the arcing contacts have separated in all poles during the subsequent opening operation.  
    • It is assumed that the opening releases incorporated in the circuit breaker are energized at the instants when the contacts touch the first pole during closing.   This represents the minimum close-open time.

    Time spread between poles

    • Time discrepancy between the contacts which is the interval time characterizing the divergence from the coincidence of connection or disconnection of the breaker contacts between the poles (non-simultaneous switching). 
    • This shall be as low as possible probably less than one peak of a half cycle.

    Static Contact Resistance-CRM

    • The measurement shall be carried out with the breaker in a closed position individually across each breaking contact.  
    • The current during the measurement shall have any convenient value,  from  50 Adc to the rated current.   
    • It shall be ensured that there is no loose connection during measurements which will lead to higher contact resistance. 
    • The measured values shall be compared with the type test results giving consideration. 
    • Any increase in contact resistance indicates the unhealthiness of the contacts.

    Dynamic contact resistance measurement-DCRM

    • Dynamic contact resistance is an effective technique for assessing the condition of circuit breaker main contacts and arcing contacts.  
    • Static contact resistance can be measured with the breaker in the closed position, but it does not give any indication of the conditions of the arcing contacts. 
    • Excessive wear & tear of the arcing contacts may lead to rupturing of the main contacts which decreases the Circuit Breaker’s Breaking capacity. 
    • To assess this only an internal inspection was done in earlier days.    However, DCRM  up to rated speed were developed to assess the condition of the arcing contacts.   
    • A current of  100A or above is applied across each of the separating contacts in a breaker pole undergoing Open or Close operation.  A resistance plot is obtained with the contacts in motion.    By assessing these plots the healthiness of the contacts can be established.

    Motor Charging time

    • Motors that are employed to charge springs shall operate satisfactorily between  85 to 110 % of rated voltage & rated frequency.
    • The consumption and time of recharging shall be measured.
    • For condition assessment of the circuit breaker, multiple tests are to be carried out.

    SUMMARY

    • The results of all the tests have to be analyzed for arriving at conclusions.  
    • Periodic condition assessment reduces the risk of unscheduled breakdown and shall be part of any regular maintenance program.

    Share. Facebook Twitter Pinterest LinkedIn Tumblr Email
    Previous ArticleFaults in Distribution Lines
    Next Article Energy Meter Apex 100
    madhusmita
    • Website
    • Facebook
    • Instagram
    • LinkedIn

    Related Posts

    Energy Meter Apex 100

    April 8, 2023

    TRANSFORMER MAINTENANCE

    December 26, 2022

    OVERVIEW OF GENERATOR PROTECTION

    December 24, 2022

    Comments are closed.

    Recent Posts
    • LIST OF B.TECH/M.TECH PROJECT IDEAS (MATLAB SIMULATION)
    • Job Opportunities for Electrical Engineers 
    • Energy Meter Apex 100
    • Testing of Circuit Breaker
    • Faults in Distribution Lines
    Recent Comments
    • Faults in Distribution Lines - Learn With Electric Know How on Distribution System Overview
    • POWER SYSTEM - Learn With Electric Know How on Distribution System Overview
    • POWER SYSTEM - Learn With Electric Know How on Thermal Power Station
    • Basics of Power System Protection - Learn With Electric Know How on OVERVIEW OF GENERATOR PROTECTION
    • Functions and Performance Requirements of Excitation Systems - Learn With Electric Know How on TYPES OF EXCITATION SYSTEM
    Archives
    • May 2023
    • April 2023
    • March 2023
    • December 2022
    • November 2022
    Categories
    • Distribution
    • Generation
    • Protection
    • Q&A
    • Switchgear
    • Transmission
    • Uncategorized
    Meta
    • Register
    • Log in
    • Entries feed
    • Comments feed
    • WordPress.org

    Quick Links

    • Home
    • About Us
    • Contact Us

    Post Categories

    • Generation
    • Transmission
    • Distribution
    • Protection
    • Switchgear
    • Q&A

    Vip Link

    • Privacy Policy
    • Disclaimer
    • Terms and Conditions

    Contact Us

    • [email protected]
    Youtube Linkedin