Close Menu
    Facebook X (Twitter) Instagram
    Trending
    • INTRODUCTION TO SUBSTATION EARTHING
    • Maintenance of GIS (Gas-Insulated Switchgear)
    • Nameplate Detail of Isolators/Dis-connectors- A Detail Guide
    • What is the use of an anti-pumping relay?
    • Key Components of Control & Relay Panel
    • TRANSMISSION TOWER CONFIGURATION
    • Nameplate Detail of Current Transformer – A Detail Guide
    • Major parameters of a circuit breaker
    Electric Know How
    • Home
    • Generation
      • Hydropower Station
      • Thermal Power Station
      • DISTRIBUTED ENERGY SOURCES
      • Diesel Generator
      • Industrial Tools
      • DC System-Generating Stations
    • Transmission
      • High Voltage DC Transmission
      • High Voltage AC Transmission
        • Transmission line – An Overview
        • TRANSMISSION TOWER CONFIGURATION
      • Three Phase Control Wiring
    • Distribution
      • Distribution System Overview
      • Faults in Distribution Lines
    • Protection
      • Power System Protection
        • Types of Fault in Power System
        • Relay Setting Calculation for Substation
        • Circuit Breaker
          • Major parameters of a circuit breaker
        • Key Components of Control & Relay Panel
      • OVERVIEW OF TRANSFORMER PROTECTION
        • Differential Protection of Transformer
      • OVERVIEW OF GENERATOR PROTECTION
      • Distance Protection
      • Electrical Safety
    • Switchgear
      • Electrical Sub-Station
        • BATTERY SYSTEM IN GRID SUBSTATION
        • Operation of Float Cum Boost Charger
        • Protection Circuitry of Battery Charger
        • Power Transformer
          • INSULATION RESISTANCE OF TRANSFORMER
          • WTI AND OTI in Power Transformer
          • Transformer Oil Dielectric strength
        • Sub-Station Operation
        • Multiplying Factor for Energy Meter
      • Current Transformer
        • Nameplate Detail of Current Transformer – A Detail Guide
      • Potential Transformer
      • Isolator in Substation
      • Electrical Busbar
      • Insulators
      • Clamps and Connectors
      • Fire Fighting System
      • Lightening Arrester
      • Gas Insulated Substation
        • Local Control Cubicle
        • SF6 circuit breaker gas compartment
    • Q&A
      • FAQS ON Current Transformer
      • POWER SYSTEM
      • FAQ ON BUSBAR
    Electric Know How
    Home»Switchgear»Energy Meter Apex 100
    Switchgear

    Energy Meter Apex 100

    madhusmitaBy madhusmita8 April 2023Updated:10 August 2023No Comments4 Mins Read
    Facebook Twitter Pinterest LinkedIn Tumblr Email
    Share
    Facebook Twitter LinkedIn Pinterest Email
    Energy Meter

    The Apex 100 Energy meter is a type of electronic energy meter used for measuring the amount of electrical energy consumed for a particular feeder in Grid Sub-Stations.

    Here is a general working principle of the Apex 100 Energy meter:

    The meter is connected to the electrical panel of a specific feeder through cables that are connected to CT and PT.

    It measures the electrical energy consumed by reading the voltage and current flowing through the circuit.

    The data is processed by an embedded microcontroller and stored in its memory.

    The meter may also have communication capabilities for remote reading and monitoring.

    The accuracy of the meter is maintained by regular calibration and testing.

    Overall, the Apex 100 Energy meter works by continuously monitoring the electrical parameters and recording the energy consumption over a given time period. This information can help individuals and organizations make informed decisions regarding energy conservation and cost management.

    Table of Contents

    Toggle
    • Wiring of Energy Meter
    • Calibration of Energy Meter

    Wiring of Energy Meter

    The wiring of the Apex 100 Energy meter may vary depending on the specific installation and electrical system. However, here are some general guidelines:

    Make sure the electrical power is turned off before beginning any wiring work.

    The meter typically has three input terminals, labeled L1, L2, and L3, for the three-phase power supply.

    The meter may also have two output terminals for the measurement of current, labeled CT1 and CT2.

    The CTs (current transformers) should be connected to the load lines, and their polarity should be observed.

    The voltage connections should be made to the L1, L2, and L3 terminals.

    It is important to note that incorrect wiring can result in damage to the meter or inaccurate readings.

    It is important to note that wiring should only be done by a qualified electrician to ensure proper installation and to prevent any damage or harm from occurring.

    Calibration of Energy Meter

    Calibrating an energy meter typically involves comparing its readings with a known reference to ensure accuracy. Here’s a general overview of the calibration process for an energy meter:

    1. Obtain a Reference Meter: You will need a calibrated reference meter that is traceable to a recognized standard. This reference meter should have higher accuracy and be calibrated by an accredited calibration laboratory.
    2. Prepare Test Setup: Set up a test bench or test environment with appropriate electrical connections, including the necessary power supply, current shunts, voltage dividers, and any other equipment needed for the specific type of energy meter being calibrated.
    3. Verify Test Bench Accuracy: Before proceeding with the calibration, verify the accuracy of the test bench or test environment by calibrating the reference meter against a known standard to ensure that it is providing accurate and reliable measurements.
    4. Connect the Energy Meter: Connect the energy meter to be calibrated to the test bench or test environment, following the manufacturer’s instructions and industry standards for electrical connections.
    5. Perform Calibration: Energize the test bench or test environment with the appropriate voltage and current levels, and record the readings from both the energy meter being calibrated and the reference meter simultaneously. Repeat the measurements for different test points or load conditions as required.
    6. Calculate Calibration Factors: Analyze the measurement data and calculate calibration factors or correction coefficients to adjust the readings of the energy meter being calibrated. This may involve using statistical methods or mathematical formulas to determine the calibration factors based on the measured values.
    7. Apply Calibration Factors: Apply the calculated calibration factors to the energy meter being calibrated, either by adjusting its settings or by applying correction factors during data analysis, depending on the type of energy meter and its calibration method.
    8. Verify Calibration: Verify the accuracy of the calibrated energy meter by comparing its readings with the reference meter at different test points or load conditions. If the readings are within the acceptable tolerance limits, the calibration is considered successful.
    9. Document Calibration Results: Record and document all calibration results, including the measurement data, calibration factors, and any adjustments made to the energy meter being calibrated. This documentation is important for traceability and quality assurance purposes.

    It’s important to note that energy meter calibration may require specialized knowledge, equipment, and expertise and should be performed by qualified personnel or accredited calibration laboratories to ensure accuracy and reliability. Always refer to the manufacturer’s instructions and industry standards for proper calibration procedures for your specific type of energy meter.

    \construction of energy meter\ \energy meter working\ energy meter energy meter reading energy meter working principle secure energy meter secure meter setting and programming in energy meter three phase energy meter
    Share. Facebook Twitter Pinterest LinkedIn Tumblr Email
    Previous ArticleTesting of Circuit Breaker
    Next Article Job Opportunities for Electrical Engineers 
    madhusmita
    • Website
    • Facebook
    • Instagram
    • LinkedIn

    Related Posts

    INTRODUCTION TO SUBSTATION EARTHING

    12 January 2025

    Maintenance of GIS (Gas-Insulated Switchgear)

    1 December 2024

    Nameplate Detail of Isolators/Dis-connectors- A Detail Guide

    11 August 2024

    Comments are closed.

    Recent Posts
    • INTRODUCTION TO SUBSTATION EARTHING
    • Maintenance of GIS (Gas-Insulated Switchgear)
    • Nameplate Detail of Isolators/Dis-connectors- A Detail Guide
    • What is the use of an anti-pumping relay?
    • Key Components of Control & Relay Panel
    Certification Course
    Archives
    • January 2025
    • December 2024
    • August 2024
    • July 2024
    • May 2024
    • March 2024
    • February 2024
    • January 2024
    • November 2023
    • October 2023
    • September 2023
    • August 2023
    • July 2023
    • June 2023
    • May 2023
    • April 2023
    • March 2023
    • December 2022
    • November 2022
    Categories
    • Distribution
    • Generation
    • Nameplate Details
    • Protection
    • Q&A
    • Switchgear
    • testing
    • Transmission
    Electric Volt

    Quick Links

    • Home
    • About Us
    • Contact Us

    Post Categories

    • Generation
    • Transmission
    • Distribution
    • Protection
    • Switchgear
    • Q&A

    Vip Link

    • Privacy Policy
    • Disclaimer
    • Terms and Conditions

    Contact Us

    • [email protected]
    Linkedin